Mecer 10kVA Plug and Play On-line Single Phase Input and Output UPS
- 10kVA / 9000 Watt
- Internal Batteries
- Higher power density, more power output
- Wider input range, higher efficiency
- Ultra low noise, multiple configurable options
- High quality LCD with wide view
Please contact us for quantity discounts
Email: info@createenergy.co.za or telephone: +(27) 11 888 0410
*Product Specifications are subject to change without prior notice.
Mecer On-Line UPS Unit is a high quality 6kVA Hardwired UPS
ME-10000-WPTV
10kVA Mecer UPS:
- 10kVA / 10000VA / 9kW (9000 Watts)
ME-9000-WPTV
- 10kVA / 9000 Watt
- Internal Batteries
- Higher power density, more power output
- Wider input range, higher efficiency
- Ultra low noise, multiple configurable options
- High quality LCD with wide view
Specifications:
Model | ME-6000-WPTV | ME-10000-WPTV |
Dimensions | 248 x 500 x616 | 248 x500 x616 |
W*D*H(mm) | ||
Weight(kg) | 58.9 | 62.1 |
Power | ||
Apparent Power(KVA) | 6KVA/ | 10KVA/ |
Active power(KW) | 5.4KW | 9KW |
Mains | ||
Voltage range | 120Vac-275Vac(phase to phase) | |
Current* | 32.1A max | 52.6 A max |
Voltage range | 40Hz-70Hz | |
Power factor | 0.99 | |
Output | ||
Rating Voltage | 230Vac(±1%) | 230Vac(±1%) |
Rating Current | 27A | 45A |
Frequency range | 50Hz x (1±1%); Follow main power in phase lock range | |
Power factor | 0.9 | |
Output Overload | 105%-125%, load transfer to bypass mode after 10 min (0-30℃) or | |
1min(30-40℃); | ||
125%-150%,load transfer to bypass mode after 30s; | ||
Over 150%, load transfer to bypass after 0.5s | ||
Load crest ratio | 3:1( max) | |
THD | <2%( 100% Line load) | |
Enviromental and safety | ||
EMC Standard | EN IEC 62040-2:2018 / EN 62040-2:2006 / IEC 62040-2:2016 | |
Safety Standard | EN62040-1:2008+A1:2013 | |
Operation temperature |
0-40 ℃ | |
Store temperature | -25℃ to 55 ℃ | |
Relative humidity | 20% to 90% | |
Altitude | <1000m | |
*The max current is under 176Vac input, full rating load and empty battery charging. |
MUST BE INSTALLED BY AN ELECTRICIAN AND UPS SPECIALIST AS PER LOCAL LAWS AND REGULATIONS
EXCLUDES DELIVERY, INSTALLATION AND COMMISSIONING
Warranties:
UPS: 12 Month Component Manufacturer's Carry In Warranty (Owing to normal use)
Internal Batteriess: 6 Months / 200 Cycles / Loadsheddings Manufacturer's Carry In Warranty (Owing to normal use)
Recharge times at C10: 8 - 14 Hours
Batteries being deeply discharged / not being fully charged correctly will shorten the life of batteries / damage batteries which is not covered by the manufacturer's warranty
When runtimes are depleted, the batteries have reached their end of life and will need to be replaced